1. 成人看片粉色视频APP,成人看片网站,免费在线看片网址,可以看片的黄色网站

      Scan code consultation:
      0755-2102 2109
      Technology
      Technology
      Current locations: Home Technology Ex tech
      Explosion proof area division for explosion-proof certification

      SINO Testing Services

      | 2024-07-29|Return

      (1) Flammable and explosiveClassification of Gas Environment Zones

      Zone 0:In normal circumstances, places where flammable and explosive gas mixtures occur continuously, frequently, or exist for a long time, such as certain parts of oil drilling platforms. Dangerous gases typically exist for at least 1000 hours per year.

      Zone 1:Under normal circumstances,inflammable and explosivePlaces where gas mixtures may occur, such as non mining faces in coal mines, enclosed areas in petroleum and petrochemical industries (with ventilation openings), etc. The existence time of hazardous gases in this area is generally between 10-1000 hours per year.

      Zone 2:Under normal circumstances,inflammable and explosiveGas mixtures are unlikely to occur and only occasionally occur for a short period of time under abnormal conditions, such as in non enclosed areas of petroleum and petrochemical plants (outdoors). The duration of existence of hazardous gases is usually ≤ 10 hours/year
      333.jpg

      (2) Classification of flammable and explosive dust environment areas

      Zone 20:Places and containers where combustible dust continuously or frequently occurs during normal operation, and its quantity is sufficient to form a mixture of combustible dust and air and/or may form uncontrollable and extremely thick dust layers. For example, internal areas of certain dust containers, storage tanks, etc. The existence time of combustible dust is ≥ 1000 hours/year.

      Zone 21:Places where combustible dust and air mixtures with combustible concentrations may be generated during normal operation. For example, places outside dust containers under specific conditions. The existence time of combustible dust is between 10-1000 hours/year.

      Zone 22:Under normal operation, combustible dust and air mixture generally do not appear, only in abnormal conditions where combustible dust occasionally appears and only exists for a short period of time. For example, when the exhaust port of the dust bag filter ventilation hole malfunctions. The existence time of combustible dust is ≤ 10 hours/year.

      It should be noted that the classification of hazardous areas should take into account factors such as the amount of flammable and explosive dust, explosion limits, and ventilation conditions. At the same time, when specific conditions are met, it can be classified as a non hazardous area.





      Related Recommendations
      Contact us
      0755-2102 2109
      Add: 13F, Building C, Kangjia Guangming Technology Center, No. 288 Xingxin Road, Guangming District, Shenzhen
      Follow us
      Copyright: Shenzhen Zhongnuo Testing Technology Co., Ltd. 粵ICP備42228678號
      Service Hotline
      18924609560
      點擊這裏給我發消息 1354407946
      點擊這裏給我發消息 1354407946
      網站地圖